Caution, Pvcheck – HT instruments PVCHECK User Manual

Page 45

Advertising
background image

PVCHECK

EN - 43

6.4.4. Measuring insulation – STRING mode

CAUTION

The maximum current which can be measured by the instrument is 10A.
Before carrying out the measures of Insulation in "STRING" mode,
always ensure that the instrument is connected to ONE STRING and not
more strings in parallel to avoid possible damage of it

1. Position the cursor onto M

 by using the arrow keys

(

,) and confirm with ENTER. The display shows the

screen to the side.

2. Press the ENTER key, activate “Settings” and possibly

change the desired parameters (see § 5.4). The following
parameters are shown on the display:

Ins. Test  selected test voltage (250, 500 or

1000VDC)

Ri min  minimum limit threshold for insulation

measurement

Mode  measuring mode: STRING
Vtest  real applied test voltage
Rp  final value of the measurement obtained by the

parallel of Ri(+) e Ri(-) values which is compared with
the Ri min limit by the instrument

  key  access to the second page with the

measured values of VPN, VEP and VEN voltages

15/05/12 15:34:26

I n s . T e s t

:

1 0 0 0

V

R l m i n

:

1 . 0

M

M o d e :

S t r i n g

V t e s t

- - -

V

R p

- - -

M

Selection

M

3. Connect the instrument to the PV module/string being tested and to the main earth

node of the system as shown in . In particular, connect the negative output pole of the
PV field to terminal N and the positive output pole of the PV field to terminal P.

CAPTION:

E: Green

cable

P: Red

cable

N: Black cable

1. Unearthed PV module/string
2. Main system earthing

Fig. 12: Instrument connection for insulation measurement in STRING mode

CAUTION

Upon pressing the GO/STOP key, different error messages can be displayed
by the instrument (see § 6.6) and, therefore, the test cannot be started. Check
and eliminate, if possible, the problem causing the error message before going
on with the test.