Operation, 5 resource block (rb) – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 14

Advertising
background image

4

OPERATION

14

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

4.5 Resource Block (RB)

The following tables list the Resource Block parameters in alphabetical order.

It describes characteristics of the Fieldbus device (e.g. device name, serial number, etc.) and is
not included in the functional tasks of the signal converter for FF.

The following tables contain short parameter description, factory settings (Initial Value (IV)) and
possible settings.

4.5.1 Foundation Fieldbus parameters for Resource Block

Foundation Fieldbus parameters for Resource Block

Parameter
DD Name

Access

Description
Settings

Initial

ALERT_KEY

ALERT_KEY

ALERT_KEY

ALERT_KEY

Alert Key

RW

The identification number of the plant unit. This information

may be used in the host for sorting alarms, etc.

0

Setting:

1...255

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

BLOCK_ERR

Block Error

R

This parameter reflects the error status associated with the

hardware or software components associated with a block. It

is a bit string, so that multiple errors may be shown.

OOS

(Out of Service)

Setting:

•

Other: Non-specific error active

•

BlockConfiguration: Error detected in block configuration

•

LinkConfiguration:Error detected in link configuration

•

SimulationActive:Simulation enabled in this block

•

LocalOverride:Output tracking or faultstate active

•

DeviceFaultState:Device faultstate set

•

DeviceMaintenance:Device needs maintenance soon

•

InputFailure:Process variable has bad status

•

OutputFailure:Failure detected in output hardware

•

MemoryFailure:Memory error detected

•

LostStaticData:Static parameters cannot be recovered

•

LostNVData: Non-Volatile parameters cannot be recovered

•

ReadbackCheck: Failure detected in READBACK

•

MaintenanceNeeded: Device NEEDS maintenance NOW

•

PowerUp: Recovery from power failure

•

OutOfService: Block actual mode is Out of Service

MODE_BLK

MODE_BLK

MODE_BLK

MODE_BLK

Block Mode

The actual, target, permitted and normal modes of the block.

TARGET

Target

RW

This is the mode requested by the operator. Only one mode

from those allowed by the permitted mode parameter may be

requested.

OOS

Setting:

•

Auto

•

OOS

ACTUAL

Actual

R

This is the current mode of the block, which may differ from

the target based on operating conditions. Its value is

calculated aa part of block execution.

OOS

Setting:

•

Auto

•

OOS

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 14 Friday, February 21, 2014 11:25 AM