background image

4

OPERATION

16

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

DISABLED

Disabled

RW

The disabled state of each alarm.

Uninitialized

Setting:

•

Disc Alm Diabled

•

Block Alm Diabled

•

Fail Alm Diabled

•

Off Spec Alm Diabled

•

Maint Alm Diabled

•

Check Alm Diabled

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

Block Alarm

The block alarm is used for all configuration, hardware,

connection failure or system problems in the block. The cause

of the alert is entered in the subcode field. The first alert to

become active will set the "Active" status in the "Status"

attribute. As soon as the "Unreported" status is cleared by the

alert reporting task, another block alert may be reported

without clearing the "Active" status, if the subcode has

changed.

UNACKNOWLEDGED

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

•

Uninitialized

•

Acknowledged

•

Unacknowledged

ALARM_STATE

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

•

Uninitialized

•

Clear-Reported

•

Clear-Not Reported

•

Active-Reported

•

Active-Not Reported

TIME_STAMP

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received – even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

SUB_CODE

Subcode

R

An enumeration specifying the cause of the alert to be

reported.

Other

Setting:

•

Other

•

BlockConfiguration

•

LinkConfiguration

•

SimulationActive

•

LocalOverride

•

DeviceFaultState

•

DeviceMaintenance

•

InputFailure

•

Output failure

•

MemoryFailure

•

LostStaticData

•

LostNVData

•

RbackCheck

•

MaintenanceNeeded

•

PowerUp

•

OutOfService

VALUE

Value

R

The value of the associated parameter at the time the alert

was detected.

0

Setting:

0...255

Foundation Fieldbus parameters for Resource Block

Parameter
DD Name

Access

Description
Settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 16 Friday, February 21, 2014 11:25 AM