02/2014 - 4001208201 - AD H250 M40 FF R02 en

AI1/2_DIAG

AI 1/2

R

reason for OUT.status not Good , bits at BLK_ERR and other

diagnosis

current diagnosis

Setting:

•

Startup Device

•

RB : MODE_BLK.ACTUAL is OOS

•

Memory failure

•

no schedule

•

period of execution

•

period of execution to large

•

MODE_BLK.PERMITTED doesn’t include Auto

•

MODE_BLK.TARGET is set OOS

•

MODE_BLK.TARGET is set MAN

•

MODE_BLK.ACTUAL is MAN , Startup to Auto

•

CHANNEL is uninitialized

•

UNIT of CHANNEL selected TB.prim_val not convertible to
XD UNIT

•

XD_SCALE : difference between EU_100 and EU_0 is to less

•

OUT_SCALE : difference between EU_100 and EU_0 is to less

•

L_TYPE is uninitialized

•

L_TYPE is direct , XD_SCALE is not equal OUT_SCALE

•

IO_OPTS no unit conversion , XD UNIT doesn’t match to UNIT
of TB.prim_val

•

SIMULATE_STATUS is not Good , Simulation is active

•

SIMULATE_STATUS imited , STATUS_OPTS is set ,
Simulation active

•

Simulation is active

•

Transducer Block MODE_BLK.ACTUAL is OOS

•

CHANNEL selected TB.prim_val.status is Bad

•

TB.prim_val.status is imited , STATUS_OPTS is set

•

CHANNEL selected TB.prim_val.status is Uncertain

•

OUT.value exceeds OUT_SCALE

•

unknown reason

•

ok

PID_DIAG

PID

R

reason for OUT.status not Good , bits at BLK_ERR and other

diagnosis

current diagnosis

Setting:

•

Startup Device

•

RB : MODE_BLK.ACTUAL is OOS

•

Memory failure

•

no schedule

•

period of execution

•

period of execution to large

•

MODE_BLK.PERMITTED doesn’t include Auto

•

MODE_BLK.TARGET is set OOS

•

MODE_BLK.TARGET is set MAN

•

MODE_BLK.ACTUAL is MAN , Startup to Auto

•

BYPASS is uninitialized

•

SHED_OPT is uninitialized

•

PV_SCALE : EU_100 <= EU_0

•

OUT_SCALE : EU_100 <= EU_0

•

TRK_SCALE : EU_100 <= EU_0

•

FF_SCALE : EU_100 <= EU_0

•

unknown reason

•

ok

Manufacturer specific parameters for Resource Block

Parameter

Parameter

Parameter

Parameter
DD Name

Access

Description
Settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 25 Friday, February 21, 2014 11:25 AM