OPERATION

26

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

IT1_DIAG

IT1

R

reason for OUT.status not Good , bits at BLK_ERR and other

diagnosis

current diagnosis

Setting:

•

Startup Device

•

RB : MODE_BLK.ACTUAL is OOS

•

Memory failure

•

no schedule

•

period of execution

•

period of execution to large

•

MODE_BLK.PERMITTED doesn’t include Auto

•

MODE_BLK.TARGET is set OOS

•

MODE_BLK.TARGET is set MAN

•

MODE_BLK.ACTUAL is MAN , Startup to Auto

•

INTEG_TYPE is uninitialized

•

IN_1 and IN_2 are not connected

•

TIME_UNIT1 and TIME_UNIT2 are uninitialized

•

CLOCK_PER <= period of execution

•

TIME_UNIT1 is uninitialized

•

TIME_UNIT2 is uninitialized

•

IN_1.status is Bad

•

IN_2.status is Bad

•

IN_1.value is NaN or INF

•

IN_2.value is NaN or INF

•

PCT_INCL < UNCERT_LIM

•

PCT_INCL < GOOD_LIM

•

PULSE_VAL1 and PULSE_VAL2 are 0

•

TOTAL_SP is 0 : cyclic reset

•

unknown reason

•

ok

DIAGNOSIS_DEV

DIAGNOSIS_DEV

DIAGNOSIS_DEV

DIAGNOSIS_DEV

diagnosis device

Display of maximum 4 error messages.

diag_enum_dev

ESK diag

R

Setting:

current diagnosis

•

Startup phase

•

F Internal communication

•

F ROM error

•

F RAM error

•

F Memory corrupted

•

F Crystal failure

•

F Invalid drift

•

F Sensor A failure

•

F Sensor B failure

•

reserved 0.7

•

S electronic temperature

•

S PV > 100%

•

S No pre-linearisation

•

S No compensation

•

S No output linearization

•

reserved 1.6

•

reserved 1.7

•

reserved 2.0

•

reserved 2.1

•

reserved 2.2

•

reserved 2.3

•

reserved 2.4

•

reserved 2.5

•

reserved 2.6

•

no message

ESK_DESCRIPTION

ESK_DESCRIPTION

ESK_DESCRIPTION

ESK_DESCRIPTION

ESK description

ESK basic module description

FIRMWARE_VER_ESK

firmware version ESK

R

Firmware version of ESK basic module

current version

SERIAL_NUM_ESK

serial number ESK

R

Serial number of ESK basis module

current serial

number

Manufacturer specific parameters for Resource Block

Parameter

Parameter

Parameter

Parameter
DD Name

Access

Description