Technical data, Technical data 2.1 foundation fieldbus data – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual
Page 6

2
TECHNICAL DATA
6
H250 M40
www.krohne.com
02/2014 - 4001208201 - AD H250 M40 FF R02 en
Technical data
2.1 Foundation Fieldbus data
Description
Type
Variable-Area Flowmeter
Physical layer
Foundation Fieldbus protocol, compliant to IEC 61158-2 and FISCO model;
galvanically isolated
Communication standard
H1
ITK version
5.2
Manufacturer ID
00012C
Device type
0700
Device revision
01
DD revision
01
CFF revision
01
Data blocks
Function blocks
1 x Enhanced Resource Block (RB)
1 x Customer Transducer Block (TB)
2 x Analog Input Block (AI)
1 x Integrator Block (IT)
1 x Proportional Integral Derivate Block (PID)
Execution time
Analog Input Block: 20 ms
Integrator Block: 25 ms
PID Block: 35 ms
Electrical connections
Device power supply
Bus powered 9...32 VDC - not intrinsically safe
Bus powered 9...24 VDC - intrinsically safe
Basic current
16 mA
Maximum error current
23 mA
Start current after 10 ms
lower than basic current
Polarity sensitivity
No
Minimum cycle time
250 ms
AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 6 Friday, February 21, 2014 11:25 AM