Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 18

Advertising
background image

4

OPERATION

18

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

FEATURES_SEL

FEATURES_SEL

FEATURES_SEL

FEATURES_SEL

Features Selection

RW

Used to select resource block options.

Reports

Faultstate

Soft W Lock

Setting:

Reports

Faultstate

Soft W Lock

MVC Report Distribution supported

MVC Publishing/Subscribing supported

Multi-bit Alarm (Bit-Alarm) Support

FREE_SPACE

FREE_SPACE

FREE_SPACE

FREE_SPACE

Free Space

R

Percent of the memory available for further configuration.

Zero in a preconfigured device.

0.0

Setting:

0.0…100.0

FREE_TIME

FREE_TIME

FREE_TIME

FREE_TIME

Free Time

R

Percent of the block processing time that is free to process

additional blocks.

0.0

Setting:

0.0…100.0

GRANT_DENY

GRANT_DENY

GRANT_DENY

GRANT_DENY

Grant Deny

RW

Options for controlling access of host computers and local

control panels to operating, tuning and alarm parameters of

the block.

GRANT

Grant

RW

Depending on the philosophy of the plant, the operator or a

higher level device (HLD) or a local operator's panel (LOP) in

the case of "Local", may turn on an item of the "Grant"

attribute - "Program, Tuning, Alarm or Local".

Uninitialized

Setting:

Program

Tune

Alarm

Local

DENY

Deny

RW

The Denied attribute is provided for use by a monitoring

application in an interface device and may not be changed by

an operator.

Uninitialized

Setting:

Program denied

Tune denied

Alarm denied

Local denied

HARD_TYPES

HARD_TYPES

HARD_TYPES

HARD_TYPES

Hardware Types

R

The types of hardware available as channel numbers.

Scalar input

ITK_VER

ITK_VER

ITK_VER

ITK_VER

ITK Version

R

Major revision number of the interoperability test case used to

register this device.

5

LIM_NOTIFY

LIM_NOTIFY

LIM_NOTIFY

LIM_NOTIFY

Limit Notify

RW

Maximum number of unconfirmed notify messages allowed.

20

Setting:

0...255

MANUFAC_ID

MANUFAC_ID

MANUFAC_ID

MANUFAC_ID

Manufacturer ID

R

Manufacturer identification number - used by an interface

device to locate the DD file for the resource.

KROHNE

MAX_NOTIFY

MAX_NOTIFY

MAX_NOTIFY

MAX_NOTIFY

Maximum Notify

R

Maximum number of unconfirmed notify messages possible.

20

Setting:

0...255

MEMORY_SIZE

MEMORY_SIZE

MEMORY_SIZE

MEMORY_SIZE

Memory Size

R

Available configuration memory in the empty resource. To be

checked before attempting a download.

0

MIN_CYCLE_T

MIN_CYCLE_T

MIN_CYCLE_T

MIN_CYCLE_T

Minimium Cycle Time

R

Time duration of the shortest cycle interval of which the

resource is capable.(in [1/32 ms])

6400

Foundation Fieldbus parameters for Resource Block

Parameter
DD Name

Access

Description
Settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 18 Friday, February 21, 2014 11:25 AM

Advertising