Operation – KROHNE H250 M40 FOUNDATION FIELDBUS User Manual

Page 41

Advertising
background image

OPERATION

4

41

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

PERMITTED

Permitted

RW

Defines the modes which are allowed for an instance of the block.

The permitted mode is configured based on application

requirement.

•

OOS

•

Auto

Setting:

•

Auto

•

OOS

NORMAL

Normal

RW

This is the mode which the block should be set to during normal

operating conditions.

Auto

Setting:

•

Auto

•

OOS

ST_REV

ST_REV

ST_REV

ST_REV

Static Revision

R

The revision level of the static data associated with the function

block. The revision value will be incremented each time a static

parameter value in the block is changed.

0

Setting:

0...65635

STRATEGY

STRATEGY

STRATEGY

STRATEGY

Strategy

RW

The strategy field can be used to identify grouping of blocks. This

data is not checked or processed by the block.

0

Setting:

0...65635

TAG_DESC

TAG_DESC

TAG_DESC

TAG_DESC

Tag Description

RW

This is the user description of the block.

blanks

Setting:

≤32 digits

ACK_OPTION

ACK_OPTION

ACK_OPTION

ACK_OPTION

Acknowledge

Option

RW

Selection of whether alarms associated with the function block

will be automatically acknowledged.

Uninitialized

Setting:

•

HiHi Alm Auto Ack

•

Hi Alm Auto Ack

•

LoLo Alm Auto Ack

•

Lo Alm Auto Ack

•

Blk Alm Auto Ack

•

Fail Alm Auto Ack

•

Off Spec

•

Alm Auto Ack

•

Maint Alm Auto Ack

•

Check Alm Auto Ack

ALARM_HYS

ALARM_HYS

ALARM_HYS

ALARM_HYS

Alarm Hystresis

RW

Amount the PV must return within the alarm limits before the

alarm condition clears. Alarm Hysteresis is expressed as a

percent of the span of the PV.

0.5

Setting:

0...50%

ALARM_SUM

ALARM_SUM

ALARM_SUM

ALARM_SUM

Alarm Summary

The current alert status, unacknowledged states, unreported

states and disabled states of the alarms associated with the

function block.

CURRENT

Current

R

The active status of each alarm.

Uninitialized

Setting:

•

HiHi Alarm

•

Hi Alarm

•

LoLo Alarm

•

Lo Alarm

•

Block Alarm

Analog Input Block

Parameter
DD Name

Access

Description
settings

Initial

AD_H250_M40_FF_R02_en_4001208201_PRT.book Page 41 Friday, February 21, 2014 11:25 AM