OPERATION

4

63

H250 M40

www.krohne.com

02/2014 - 4001208201 - AD H250 M40 FF R02 en

CONTROL_OPTS

CONTROL_OPTS

CONTROL_OPTS

CONTROL_OPTS

Control Options

Control Options

Control Options

Control Options

RW

Options which the user may select to alter the calculations

done in a control block.

No option selected

Setting:

•

Bypass Enable: This parameter, if true, allows BYPASS to be
set. Some control algorithms cannot provide closed loop
control if bypassed.

•

SP-PV Track Man: Permits the setpoint to track the process
variable when the block mode is "Man".

•

SP-PV Track ROut: Permits the setpoint to track the process
variable when the block mode is "ROut".

•

SP-PV Track LO-IMan: Permits the setpoint to track the
process variable when the block mode is "LO or IMan".

•

SP Track retain: Permits the setpoint to track the RCas or
Cas parameter based on the retained target mode when the
actual mode of the block is "Man, LO, Man, or Rout".

•

Direct acting: Defines the relationship between changes in
PV and changes to output - when direct is selected, an
increase in PV results in an increase in the output.

•

Track enable: This enables the external tracking function –
when TRK_ENA is 1, the preset value in TRK_VAL is output if
TRK_IN_D becomes true.

•

Track in manual: This is used only if TRK_ENA is YES (1) -
when the block mode is Man, TRK_IN_D will be acted on only
if the TRK_OVMAN control option is set.

•

PV for BKCal_Out: The BKCAL_OUT value may be selected
as the working SP or the PV - normally, BKCAL_OUT is the
working SP.

•

Restrict SP to limits in Cas and RCas: If this option is
selected, the setpoint will be restricted to the setpoint
absolute and rate limits in Cas and Rcas modes.

•

No output limits in Man: Do not apply OUT_HI_LIM or
OUT_LO_LIM when target and actual modes are "Man".

DV_HI_ALM

DV_HI_ALM

DV_HI_ALM

DV_HI_ALM

Deviation High

Deviation High

Deviation High

Deviation High

Alarm

Alarm

Alarm

Alarm

The status and time stamp associated with the high deviation

alarm.

Unacknowledged

RW

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

•

Uninitialized

•

Clear - reported: Alarm not active and reported

•

Clear - not reported: Alarm not active and not reported

•

Active - reported: Alarm active and reported

•

Active - not reported: Alarm active and not reported

Proportional Integral Derivative Block

Parameter
DD Name

Access

Description
settings

Initial Value