Industrial Registers, Models ER-420-AC, ER-420-DC & ER-420-LP

2 – FLOW RATE

The settings for Total and Flow Rate are entirely separate In this way, different units of measurement can be used, for example, USGAL for

Total and barrels for Flow Rate The display update time for Flow Rate is one sec or more

OTEE:

N

These settings also influence the analog output

MEASUREMENT UNIT

21

SETUP 21 determines the measurement unit for flow rate
The options are:

mL, L, m

3

, mg, g, kg, ton, GAL, bbl, lb, cf, REV, no unit, scf, Nm

3

, NL, P, MGAL

Alteration of the measurement unit will have consequences for operator and Setup level values Please note

that the K-factor has to be adapted as well; the calculation is not done automatically

TIME UNIT

22

The flow rate can be calculated per sec (SEC), minute (MIN), hour (HR) or day (DAY)

DECIMALS

23

This setting determines for flow rate the number of digits following the decimal point

The options are:

00000, 1111 1, 2222 22, 3333 333

K-FACTOR

24

With the K-factor, the flowmeter pulse signals are converted to a flow rate The K-factor is based on the

number of pulses generated by the flowmeter per selected measurement unit (SETUP 21), for example per

liter The more accurate the K-factor, the more accurate the functioning of the system will be For examples

read SETUP 13

DECIMALS K-FACTOR

25

This setting determines the number of decimals for the K-factor (SETUP 24) The options are:

0, 1, 2, 3, 4, 5, 6
This SETUP indirectly influences the accuracy of the K-factor This setting has NO influence on the displayed

number of digits for flow rate (SETUP 23)!

CALCULATION

26

The flow rate is calculated by measuring the time between a number of pulses, for example 10 pulses The

more pulses the more accurate the flow rate will be The maximum value is 255 pulses
NOTESE:
• This setting does influence the update time for the analog output directly (maximum update 10 times a

sec) If the output response is too slow, decrease the number of pulses

• For low frequency applications (below 10 Hz): do not program more than 10 pulses else the update time

will be very slow

• For high frequency application (above 1 kHz) do program a value of 50 or more pulses

CUT-OFF TIME

27

With this setting, you determine a minimum flow requirement thresh-hold, if during this time less than XXX-

pulses (SETUP 26) are generated, the flow rate will be displayed as zero

The cut-off time has to be entered in secs

The maximum time is 999 secs (about 15 minutes)

3 – DISPLAY

FUNCTION

31

The large 17 mm digits can be set to display total or flow rate

When you select Total, both the total and the flow rate display simultaneously

When you select Flow Rate, only flow rate and its measuring unit display Press Select to display the total

4 – POWER MANAGEMENT (DOES NOT APPLY TO THIS UNIT)

Page 16