Industrial Registers, Models ER-420-AC, ER-420-DC & ER-420-LP

Terminal 07-08 analog output (SETUP 7) :

A passive 4-20 mA signal proportional to the flow rate is available with this option When a power supply is connected but the

output is disabled, a 3 5 mA signal will be generated
Maximum driving capacity is 1000 Ohm This output does loop power the unit as well

Terminal 09-11; Flowmeter input:

Two basic types of flowmeter signals can be connected to the unit: passive or active pulse
The screen of the signal wire must be connected to the common ground terminal 9 (unless earthed at the sensor itself)
The maximum input frequency is approximately 10 kHz (depending on the type of signal) The input signal type has to be

selected with the correct SETUP function (see

"Details of Setup Functions" on page 15

)

Pulse-signal NPN / NPN-LP:

The ER-420 is suitable for use with flowmeters which have a NPN output signal For reliable pulse detection, the pulse

amplitude has to go below 1 2V Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input

frequency (see

"Details of Setup Functions" on page 15

)