6 – ANALOG OUTPUT

FILTER
67

This function is used to stabilize the analog output signal The output value is updated every

0 1 sec With the help of this digital filter a more stable but less precise reading can be obtained
The filter principal is based on three input values: the filter level (01…99), the last analog output value and

the last average value The higher the filter level, the longer the response time on a value change will be
Below, several filter levels with their response times are indicated:

RESPONSE TIME ON STEP CHANGE OF ANALOG VALUE. TIME IN SecS

FILTER VALUE

50% INFLUENCE

75% INFLUENCE

90% INFLUENCE

99% INFLUENCE

01

filter disabled

filter disabled

filter disabled

filter disabled

02

0 1 sec

0 2 sec

0 4 sec

0 7 sec

03

0 2 sec

0 4 sec

0 6 sec

1 2 sec

05

0 4 sec

0 7 sec

1 1 sec

2 1 sec

10

0 7 sec

1 4 sec

2 2 sec

4 4 sec

20

1 4 sec

2 8 sec

4 5 sec

9 0 sec

30

2 1 sec

4 sec

7 sec

14 sec

50

3 5 sec

7 sec

11 sec

23 sec

75

5 2 sec

10 sec

17 sec

34 sec

99

6 9 sec

14 sec

23 sec

45 sec