6 – ANALOG OUTPUT
FILTER
67
This function is used to stabilize the analog output signal The output value is updated every
0 1 sec With the help of this digital filter a more stable but less precise reading can be obtained
The filter principal is based on three input values: the filter level (01…99), the last analog output value and
the last average value The higher the filter level, the longer the response time on a value change will be
Below, several filter levels with their response times are indicated:
RESPONSE TIME ON STEP CHANGE OF ANALOG VALUE. TIME IN SecS
FILTER VALUE
50% INFLUENCE
75% INFLUENCE
90% INFLUENCE
99% INFLUENCE
01
filter disabled
filter disabled
filter disabled
filter disabled
02
0 1 sec
0 2 sec
0 4 sec
0 7 sec
03
0 2 sec
0 4 sec
0 6 sec
1 2 sec
05
0 4 sec
0 7 sec
1 1 sec
2 1 sec
10
0 7 sec
1 4 sec
2 2 sec
4 4 sec
20
1 4 sec
2 8 sec
4 5 sec
9 0 sec
30
2 1 sec
4 sec
7 sec
14 sec
50
3 5 sec
7 sec
11 sec
23 sec
75
5 2 sec
10 sec
17 sec
34 sec
99
6 9 sec
14 sec
23 sec
45 sec