Industrial Registers, Models ER-420-AC, ER-420-DC & ER-420-LP

6 – ANALOG OUTPUT

A linear analog 4-20 mA signal is generated according to the Flow Rate with a 10 bits resolution The settings for Flow Rate (SETUP 2)

influence the analog output directly The relationship between rate and analog output is set with the following functions:
DISABLE / ENABLE
61

The analog output can be disabled When disabled, a 3 5 mA will be generated if a power supply is available

MINIMUM FLOW RATE
62

Enter here the flow rate at which the output should generate the minimum signal (4 mA)—in most

applications, at flow rate "zero" The number of decimals displayed depends upon SETUP 23 The time and

measuring units (L/min for example) are dependant upon SETUP 21 and 22 but are not displayed

MAXIMUM FLOW RATE
63

Enter here the flow rate at which the output should generate the maximum signal (20 mA)—in most

applications at maximum flow The number of decimals displayed depends upon SETUP 23 The time and

measuring units (L/min for example) are dependant upon SETUP 21 and 22 but cannot be displayed

CUT-OFF
64

To ignore leakage of the flow for example, a low flow cut-off can be set as a percentage of the full range of 16

mA When the flow is less than the required rate, the current will be the minimum signal (4 mA)
Examples:

4 mA

(SETUP 62)

20 mA

(SETUP 63)

CUTOFF

(SETUP 64)

REQUIRED RATE

OUTPUT

0 gpm

100 gpm

2%

(100-0)*2% = 2 0 gpm

4+(16*2%) = 4 32 mA

20 gpm

800 gpm

3 5%

(800-20)*3 5%= 27 3

gpm

4+(16*3 5%) = 4 56 mA

TUNE MIN / 4 mA
65

The initial minimum analog output value is 4 mA However, this value might differ slightly due to external

influences such as temperature The 4 mA value can be tuned precisely with this setting

BEFORE TUNING THE SIGNAL, BE SURE THAT THE ANALOG SIGNAL IS NOT BEING USED FOR ANY

APPLICATION!
After pressing PROG, the current will be about 4 mA The current can be increased / decreased with the

arrow-keys and is directly active Press ENTER to store the new value
The analog output value can be programmed “upside-down” if desired, so 20 mA at minimum flow rate for

example!

TUNE MAX / 20 mA
66

The initial maximum analog output value is 20 mA However, this value might differ slightly due to external

influences such as temperature for example The 20 mA value can be tuned precisely with this setting

BEFORE TUNING THE SIGNAL, BE SURE THAT THE ANALOG SIGNAL IS NOT BEING USED FOR ANY

APPLICATION!
After pressing PROG, the current will be about 20 mA The current can be increased or decreased with the

arrow keys and is directly active Press ENTER to store the new value
The analog output value can be programmed “upside-down” if desired, so 4 mA at maximum flow rate for

example!