5 – FLOWMETER

SIGNAL

51

The ER-420 is able to handle several types of input signal The type of flowmeter pickup / signal is selected

with SETUP 51

OTEE:

N

The selections "active pulse" offer a detection level of 50% of the supply voltage Read also par

4 4 2 2 and 4 4 3 2 Flowmeter input terminal 09-11

Type of Signal

Explanation

Resistance

Freq. / MV

Remark

NPN

NPN input

100 K pull-up

6 kHz

(open collector)

NPN - LP

NPN input with low pass filter

100 K pull-up

2 2 kHz

(open collector) less

sensitive

REED

Reed switch input

1 M pull-up

1 2 kHz

REED - LP

Reed switch input with low pass

filter

1 M pull-up

120 Hz

Less sensitive

PNP

PNP input

100 K pull-down

6 kHz

PNP - LP

PNP input with low pass filter

100 K pull-down

700 kHz

Less sensitive

ACT_8 1

Active pulse input 8 1V DC

3 K9

10 kHz

External power required

ACT_12

Active pulse input 12V DC

4 K

10 KHz

External power required

ACT_24

Active pulse input 24V DC

3 K

10 KHz

External power required