Industrial Registers, Models ER-420-AC, ER-420-DC & ER-420-LP

Reed switch

The ER-420 is suitable for use with flowmeters which have a reed switch To avoid pulse bounce from the reed switch, select

REED LP – low-pass filter (see

"Details of Setup Functions" on page 15

) Transmitter wire pairs to terminals are either green and

white or black and blue

ER-420-DC and ER-420-AC
The following terminal connectors are available:

Figure 7: Overview terminal connectors AC or DC powered ER-420

Voltage selection sensor supply

With the ER-420-DC and ER-420-AC, a real power supply for the sensor is available The flowmeter can be powered with

8 2 to 12 or 24 V DC Total power consumption: max 400 mA@24V The voltage is selected with the three switches inside

the enclosure

• BE SURE THAT ALL THE LEADS TO THE TERMINALS ARE DISCONNECTED FROM THE UNIT WHEN THE INTERNAL PLASTIC

PROTECTION COVER HAS BEEN REMOVED !

• HIGH VOLTAGE 400V !! NEVER CONNECT THE MAIN POWER SUPPLY TO THE UNIT WHEN THE PLASTIC PROTECTION

COVER HAS BEEN REMOVED !!!

FIRST, REMOVE THE TERMINAL STRIP(S) AFTER WHICH THE INTERNAL PLASTIC COVER CAN BE REMOVED. THE SWITCHES

ARE LOCATED ON THE RIGHT HAND (TYPE PF / PM) AS INDICATED:

Figure 8: Switch setting sensor supply voltage ER-420-DC / ER-420-AC