Badger Meter Registers User Manual

Page 29

Advertising
background image

User Manual

Switch positions

Sensor A

Sensor B

Voltage Selection

Switch 1

Voltage

Switch 2

Voltage

Switch 3

Switch 4

Voltage

internal

3 2V DC

on

on

8 2V DC

external

switch 3+4

on

off

12V DC

off

off

2 V DC

• Function switch 1: voltage selection sensor A, terminal 11
• Function switch 2: not available for this model
• Function switch 3+4: the combination of these switches determine the voltage as indicated Do move switch 1 and / or

switch 2 to the OFF position to enable the selected voltage with switch 3+4

Terminal connections ER-420-DC and ER-420-AC

Terminal GND 01 - 02: Power Supply available only with type PD/PF or PM:

Type

Sensor Supply

Terminal

GND

01

02

ER-420-DC 24V AC ±15%

8 2, 12, 24V max 400 mA

AC

AC

ER-420-DC 24V DC ±15%

8 2, 12, 24V max 400 mA

L–

L+

ER-420-AC 115-230V AC ±15%

8 2, 12, 24V max 400 mA

EARTH

AC

AC

Note PF / PM: The total consumption of the sensors and outputs may not exceed 400 mA@24V

Terminal 05-06 scaled pulse output R1

SETUP 7 determines the pulse output function The maximum pulse frequency of this output is 500 Hz for units with Rev 03

and newer (60 Hz for units earlier than Rev 03) However, with the mechanic output option supplied, be sure that the output

frequency does not exceed 5 Hz or else the lifetime of the relay will be reduced significantly An isolated mechanical relay

output is available for the ER-420-DC and ER-420-AC Maximum switch power is 240V 0 5A per output

Terminal 07-08 analog output (SETUP 7)
• An isolated 4…20 mA signal proportional to the flow rate is available for the ER-420-DC and ER-420-AC
• When the output is disabled, a 3 5mA signal will be generated on these terminals
• Maximum driving capacity is 1000 Ohm @ 30V DC

Page 29

May 2014