Industrial Registers, Models ER-420-AC, ER-420-DC & ER-420-LP

Terminal 09-11 flowmeter input
• Two basic types of flowmeter signals can be connected to the unit: passive or active pulse
• The screen of the signal wire must be connected to the common ground terminal 9 (unless earthed at the sensor itself)
• The maximum input frequency is approximately 10 kHz (depending on the type of signal) The input signal type has to be

selected with the correct SETUP-function (see

"Details of Setup Functions" on page 15

)

Pulse-signal NPN / NPN-LP

The ER-420 is suitable for use with flowmeters which have a NPN output signal For reliable pulse detection, the pulse

amplitude has to go below 1 2V Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input

frequency (see

"Details of Setup Functions" on page 15

)