Emu status reporting, Figure 3–5 emu status leds, Emu status reporting –14 – HP Array Controller HSG V8.7 Software User Manual

Page 70: Environmental monitoring unit

Advertising
background image

Environmental Monitoring Unit

3–14 UltraSCSI RAID Enclosure

Starts the EMU timer if: (1) all blowers in a shelf bank are
defective, or (2) a blower is removed.

Approximately eight minutes after the EMU timer begins
operating, the array controllers will shut down and then the EMU
turns O

FF

the dc power in the enclosure to prevent continued

overheating and potential equipment damage.

Momentarily depressing the alarm control switch causes the EMU
audible alarm to turn O

FF

, but the fault status LEDs remains O

N

. At

this time, the blower LEDs display system fault codes that are
essential to pinpointing the fault. See the Configuration Fault Code
Reporting
section within this chapter.

EMU Status Reporting

The EMU processes subsystem status reports and notifies the user of
problems via an EMU audible alarm and EMU status LEDs. Figure
3–5
identifies the numerous EMU status LEDs.

Figure 3–5

EMU Status LEDs

The EMU processes two types of problems:

Error conditions—involves the failure of a component or
conditions outside the predetermined environment, such as an
overtemperature condition.

If an error condition is detected, the system fault LED
(C

ALLOUT

1) turns O

N

. For detailed information about other

system fault LED indications, see the Error Condition Reporting
section within this chapter.

Figure C

ALLOUTS

1.

System fault LED

2.

Alarm control
switch

3.

Temperature LED

4.

Power LED

5.

Blower LEDs

1

2

3

4

5

6

7

8

CXO5748B

4

1

2

3

5