Vaisala viewLinc 4.3 User Manual

Page 177

Advertising
background image

Installing viewLinc

viewLinc 4.3

4

|

4

169

openssl s_client -connect viewlinc.bigpharma.com:443

Note: Minimum requirements are OpenSSL 0.9.8h-1 or higher for

Windows installed.

Q:

How can I use the Mobile Application when my Smart Phone

does not have VPN access to the company network?

A:

Ask your IT department to set up port forwarding for the internal

address of the CMS server on the corporate firewall, and specify the TCP
port that the CMS has been set up to use. This port may be changed in
the viewLinc.cfg file if required.

[web]

# port for insecure (http) communications

port = 80

# port for secure (https) communications

https_port = 443

A service restart is required following this change (Options | System
Configuration | Preferences: Options | Restart viewLinc Service

)

Q:

Can I turn off the Mobile Application?

A:

The viewLinc.cfg file contains the entry to enable/disable Mobile

applications. Add a # to the start of line that contains mobile_agent_

ids. Eg #mobile_agent_ids

.

Q:

How do I keep my Security Key files when upgrading from

viewLinc 4.0 to viewLinc 4.3?

A:

There is an installation bug in viewLinc 4.0. For this version viewLinc

will load the key files fom this location:

<installdir>\Python\Lib\site-packages\viewlinc\config\keys

When creating your replacement key files, always put them in the above
folder AND in the documented folder

<datapath>\config\keys

The keys need to go in both is because upgrading viewLinc will destroy
the <installdir>\Python folder tree, thereby deleting your key files.
viewLinc 4.1 uses the correct location, so will find your key files in the
folder.

Advertising