Appendix D. Setting Up RF401-to-CR206(X) Communications

D.3 Example Setup 2 - Router to CR206(X)

The following is a typical setup of an RF401 cabled to a router datalogger and

linked to a CR206(X) in a PakBus network.

CR206(X) Example Setup 2 (see FIGURE D-6)

1. Enter PakBus Address 1.

2. Select PakBus Aware for RF Protocol.

3. Select Hop Sequence 0.

4. Select Network (Address) 0.

5. The Radio Address is fixed at 0 when the RF Protocol is PakBus.

6. Select Power Mode 1 Sec with Long Header to economize station power.

FIGURE D-6. DevConfig Deployment panel for CR206(X) Example

Setup 2

D-7