Voltage Checks
120 VAC Systems
240 VAC Systems
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
Line 1 and Neutral
120VAC (108VAC-132VAC)
GND
Ground and Line 1
120VAC (108VAC-132VAC)
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
GND
Ground and Neutral
0 Volts
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
GND
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
Line 1 and Neutral
120VAC (108VAC-132VAC)
GND
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
Line 1 and Line 2
240VAC (216VAC-264VAC)
GND
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
Ground and Neutral
0 Volts
GND
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
Line 2 and Neutral
120VAC (108VAC-132VAC)
GND
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
Line 1 and Ground
120VAC (108VAC-132VAC)
GND
F6 0.3A 250V
J44
J24
J45
F5 30A
GND
K3
K5
HTR
A
HTR
B
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
S1
S6
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22112_A
L2
L1
N
Line 2 and Ground
120VAC (108VAC-132VAC)
Set voltmeter to AC Volts. Voltages should
check out as follows:
Line 1 Black to Line 2 Red – 240VAC:
t
(Range of acceptability: 216VAC – 246VAC)
Either Line to Neutral – 120VAC
t
(Range of acceptability: 108VAC – 132VAC)
Either Line to Ground – 120VAC
t
(Range of acceptability: 108VAC – 132VAC)
Neutral to Ground – 0 Volts
t
These readings should be consistent at
all points in all electrical enclosures and
breaker boxes. If the readings are not in
the acceptable ranges, do not power up
the system.