Myron L 729II User Manual

Page 54

Advertising
background image

50

J. REMOTE ALARM - RA™

RA

Ordered as an accessory, includes 8” harness with

connector, and two (2) wire nuts.

1. DESCRIPTION

This remotely mounted AUDIBLE and VISUAL alarm con-

nects to any Myron L Company Monitor/controller, or brand “X”

controller with dry contacts. When activated by the controller the

Remote Alarm will provide both an audible and a visual alert at a

location other than at the controller.

A mute button will silence the piezo alarm for up to 10 minutes

while the LED remains illuminated. After the preset time the

piezo alarm will again sound, this will repeat until the water

quality is corrected. Thus allowing servicing of the system under

control, while still acting as a reminder if the problem has not

been corrected.

The Remote Alarm - RA™ is an inexpensive way to alert per-

sonnel of a trouble situation. For example; the Monitor/controller

may be located with an RO system while the service technicians

are on another floor or even in another building - great for hos-

pitals. The AUDIBLE alarm may be silenced, but stays in alarm

(RED LED is still illuminated) until the trouble is corrected. The

timer may be set from 15 seconds up to 10 minutes, thereby,

giving personnel the time to correct the problem while not being

able to ignore the trouble because of the reoccurring AUDIBLE

and VISUAL alerts.

Specifications

Audible Alert — Piezo Electric

Oscillating Frequency — 3.0±0.5KHz

Operating Voltage (750II) — 24VDC Nom.

(1.5-30VDC Max.)

Sound Pressure Level (Min) 30cm/12VDC — 80dB

Current consumption (Max) @ 12VDC — 12mA

Tone — Constant

Operating Temperature — -20 - +60°C

Size — 24 x 9.5 mm

Visual Alert — Bright RED LED

Time Delay — 15 seconds to 10 minutes (USER adjustable)

Power — 24VDC (supplied from Monitor/controller)

Case Material — ABS plastic

Dimensions — 4.75L x 2.56W x 1.56H (121L x 65W x 40H)

Mounting — Customer supplied screws

Operational Distance — Wire lengths of 500 feet (152 meters)

have been tested with no adverse effects

Additional Wire available, order RAW-200. — 200 feet (61 meters)

2. INSTALLATION

Briefly —

Only 2 wires to connect from the controller to the RA.

Set the time.

Mount on the wall or on the bench.

WARNING: BEFORE STARTING, IF MONITOR/

CONTROLLER IS INSTALLED, ENSURE THE POWER

IS OFF. FAILURE TO DO SO COULD CAUSE DAMAGE

TO THE INSTRUMENT, AND COULD BE HARMFUL

OR FATAL TO PERSONNEL. ONLY QUALIFIED

PERSONNEL

SHOULD

INSTALL

ELECTRICAL

EQUIPMENT.

The Remote Alarm - RA connector is labeled 24VDC INPUT and

has a 8” 2 conductor wires attached — Black is Positive (+) and

White is Negative (-).

When extending the wires you may use any two color wire you

wish just remember the polarity — Black is Positive (+) and

White is Negative (-). Wire lengths of 500 feet/152 meters have

been tested and have no adverse effect on performance although

a length of 500 feet/152 meters would be unusually long.

Ensure the unit is completely wired, tested and adjusted before

installing RA to mounting surface.

For OEM models skip steps referencing enclosure or front panel.

1. Run #22, 2 conductor speaker type wire, NOT

supplied, from Monitor/controller to RA location as

necessary. Wire may be ordered from the

Myron L Company, part #RAW-200.

2. Open the RA by removing the four (4) screws.

3. Locate and remove the 8” 2 conductor wire with the

reddish brown connector attached to the RA.

See figure III.J.1.

4. At the RA, connect the extension wires to the

connector on the RA circuit board — Black to Positive (+)

and White to Negative (-) as shown in figure III.J.1.

5. Using a standard slot screwdriver remove the two (2)

screws on the Myron L Monitor/controller front panel.

6. Carefully wiggle the front panel to loosen and pull

gently toward you. Do not pull more than about

8 inches/20CM or you could damage the wiring

harness.

7. Connect the extension wires to the 8” 2 conductor wire

with the wire nuts provided — Black to Positive (+) and

White to Negative (-). Be sure to first pass the wire

through the user supplied waterproof strain relief in the

enclosure.

8. Plug the reddish brown connector into the male connector

on the controller circuit board marked RA (see inside case

label or figure III.J.2 for location). It will only go on the

connector one way.

9. To test, simply turn ON the controller and adjust

controller set point until the alarm sounds off*. If

controller is not yet connected to water, on conductivity/

TDS controllers it will be necessary to press and hold the

Full Scale Test Switch. See figure III.J.2. The

black button on the front of the RA will mute the piezo

!

CAUTION - READ FOLLOWING CAREFULLY

RA CB ASSEMBLY

CONTROLLER

+ -

10

4

15

30

7

8

5

9

3

2

1

6

MIN

SEC

Figure III.J.1

Advertising