I/O control signals (summary)

Detailed explanations of the I/O control signals can be
found in the manual for the SPC200. A detailed sum-
mary of the I/O assignment is shown in section 4.4.2.

Start/stop mode

Address *)

Control signal

Description

I10.0

ENABLE

Enable controller (1=controller enabled)

I10.1

START/RESET

Start/continue programs or
reset (RESET in conjunction with STOP=0)

I10.2

STOP

Stop program run (0=stopped)

I10.3/I10.4

SYNC_A/B

Synchronization input for M00

Q10.0

READY

System ready

Q10.1/Q10.2

SYNC_OA/B

Synchronization output for M00

Q10.3/Q10.4

MC_A/B

MC output for program A/B (motion complete)

*) Address specifications as seen by SPC200

Record select mode

Address *)

Control signal

Description

I10.0

ENABLE

Enable controller

I10.1

RESET

Reset programs
(in conjunction with STOP=0)

I10.2

STOP

Stop positioning task (0=stopped)

I10.3/I10.4

CLK_A/B

Start NC record from program A/B

I11.0 ... I11.15

RECBIT1...10

Bits for NC record number (RECBIT1 for 2

0

etc.)

Q10.0

READY

System ready

Q10.1/Q10.2

ACK_A/B

Task accepted for program A/B

Q10.3/Q10.4

RC_A/B

NC record concluded by program A/B

*) Address specifications as seen by SPC200

4. Commissioning

4-6

SPC200-COM-IBS 0503a