5.2 On-the-spot diagnosis

The four LEDs on the field bus module permit a
speedy on-the-spot diagnosis of the communication
status. Note also the LEDs on the other modules of the
SPC200 and their description in the user manual for the
SPC200.

LED displays on the field bus module type
SPC200-COM-IBS

RD LED

RC LED

BA LED

Operating status

out

out

out

No voltage

flashes
slowly

Field bus module waits for parameter data of the
SPC200

flashes
fast

Parameter error. Operating mode, process data size
incorrectly set or not yet parametrized.

on

out

out

Field bus card ready for bus operation, but still no
physical connection to the INTERBUS.

on

on

out

Connection to the INTERBUS but still no data
exchange (bus inactive).

out

on

out

Connection to the INTERBUS but no data exchange
(bus inactive)

out

on

on

INTERBUS active, normal operating status

– = Status of the LED is not relevant

Fig. 5/1: Meaning of the LEDs on field bus module type SPC200-COM-IBS

5. Diagnosis and error treatment

5-4

SPC200-COM-IBS 0503a