6. Commissioning, operation

GB

The cable must not be shielded, however, should not be laid directly besides strong

electrical interference sources either. Including line resistance, contact resistance goes

the maximum line length and with that by the following table the maximum:

Wire cross section

in mm²

Wiring length

in m

Wiring resistance

in Ω

0.5

175

6.3

0.75

300

7.2

1.0

400

7.2

1.5

600

7.2

A complete resistance of 9 Ω, inclusive of contact resistances, should not be exceeded

since otherwise a failure signal is carried out.

In addition, for the explosion-protected version, a max. inductance of

L

a

≤ 0.5 mH and a max. capacitance of C

a

≤ 3 µF must be observed (incl.

switching amplifier values).

Connection diagram transducer and switching amplifier

For the explosion-protected version, a light-blue cable or one marked

light-blue must be installed from the switching amplifier to the transducer

(intrinsically safe circuit). The switching amplifier is located in the

non-hazardous area and the measuring body of the transducer in a Zone 1

area.

Ex zone 0/1

Safe area

Transducer

model LSO.06

Switching amplifier model LSO.25

Signal

Failure

The instrument can

be connected to

earth.