Configuration – WIKA LSO.25 User Manual

Page 29

Advertising
background image

WIKA operating instructions models LSO.06, LSO.25

29

13334603.01 09/2010 GB/D/F/E

GB

Conditions:

P1 and P2 middle position, ca. 3 - 4 s time delay if P2 is open

Transducer correct connected and in function

No failure present

The time delay is, with S2 open, = switched on, must sufficiently be pushed for a long time

the button so that the complete test can go off. No test can go off, the alarm was already

entitled taken there is with S1 open, S2 open and sensor tip immersed. The same applies

S1 closed, S2 open and sensor tip dry. Failure, LED red and a yellow one flashes, can go

off no test at.

The test function makes possible a checking the measuring chain switching amplifier

separately and e.g. post-connected signal amplifier, signaling devices, control devices or a

correction device at a connected and operating transducer and a reliable information gives

about the proper function of the circuit board.

7.5 Operating characteristics relay SIGNAL

see table "Fault effect to dry/immersed", page 25

7.6 Operating characteristics relay FAILURE

The relay failure is energized in the normal operation and releases under the following

conditions (fail safe behavior):

The supply voltage breakes down (>100 ms)

The internal supply voltage for the intrinsic safe circuit breakes down

Short circuit (BR-WS) or interruption to infrared-LED (BR)

Short circuit (GN-WS) or interruption to phototransistor (GN)

Behavior of the LED's see table "Fault effect to dry/immersed", page 25