GB

7. Configuration

7.1 Setting of fail-safe direction with switch S1

Switch S1 is a wire-hook switch which may be shortened by soldering or permanent

opened by cutting the switch wire.

High alarm:

- S1 open,

- Signal relay released if sensor tip is immersed

Low alarm:

- S1 closed

- Signal relay released if sensor tip is dry

Factory setting: - S1 open

Fault effect to dry/immersed

Operating status S1

Yellow LED

immersed

Yellow LED

dry

Signal relay

Immersed

sensor tip in

medium with higher

refractive index

open

H

High alarm

flashing

off

released

closed

L

Low alarm

permanent on

off

energized

Dry

sensor tip in

medium with lower

refractive index

open

H

High alarm

off

permanent on

energized

closed

L

Low alarm

off

flashing

released

Tr

ans

-

ducer

75 high

Fuse

M20 x 1.5 or

M16 x 1.5

time delay on

time delay off

time delay

Supply

Failure

Signal