Condition Monitoring Unit CMU 1000

Page 103

Revised 17.12.2009

HYDAC ELECTRONIC GMBH Mat.-No.:

669749

7.8 Other Boolean Operations

7.8.1 Note Value

The Note value function is used to hold on to a Boolean value (to
freeze it). It has two Boolean inputs.

If the input value x

2

is "1", then the input value x

1

is output at the

output. If the input value x

2

is "0", then the last output value remains

in effect.

If the value is only to be applied for one flank, then you can put the
function Pulse generation upstream at x

2

(see Chap. 7.8.6).

Inputs x

1

:

Value

(Boolean)

x

2

:

Note

(Boolean)

Outputs: y:

(Boolean)

Parameters: -


7.8.2 Switching Delay

The Switching delay function is used to delay Boolean signals. The
function has one Boolean input and one Boolean output. A change
at the input will not be recognizable at the output until after a
parameterizable delay time has elapsed.

The delay times can be set separately for switching on and
switching off. . They are adjusted with the parameters Switch-on
delay

and Switch-off delay. This makes it possible to suppress short-

term signal changes from view.

Example:
Input and output are "0", the switch-on delay is set to 5 seconds. If
the input switches now to "1", then the output waits 5 seconds
before switching to "1". If the input switches back to "0" before the 5
seconds have elapsed, then the input remains set to "0" and the
change at the input is not visible at all at the output.

Inputs: x:

(Boolean)

Outputs: y:

(Boolean)

Parameters: p

1

:

Switch-on delay

in seconds (Numerical)

p

2

: Switch-off

delay

in seconds (Numerical)