7.10 Actions

7.10.1 Setting Switching Output

The Set switch output function transmits the Boolean input to a
digital switching output on the CM device.

The Output terminal parameter is used to define which digital output
port is used.

Inputs: x:

(Boolean)

Outputs: -
Parameters: p

1

:

Output terminal

(input list)


7.10.2 Setting Analog Outputs

The Set analog output function outputs the numerical input to an
analog output of the CM device.

The Output parameter is used to define which analog output will be
used. The scaling is defined by the parameters Lower value and
Upper value

.

If for example -25 is set for the lower value and 150 for the upper
value, then all input values less than or equal to
-25 will cause the lower signal range to be output at the output (type
0 V or 4 mA) and all input values greater than or equal to 150 will
lead to an output signal that corresponds to the upper signal range.
(Type 10 V or 20 mA)

Inputs: x:

(Numerical)

Outputs: -
Parameters: p

1

:

Output

(input list)

p

2

:

Low range

(Numerical)

p

3

:

High range

(Numerical)