Installation

NOTICE
The front and rear of the unit should be free of obstructions to airflow. Proper ventilation
must be maintained, regardless of mounting or orientation.

2.4 Wire

Sizing


Care must be taken to properly size all conductors for the input and output of the power
supply. Table 2.4-1 gives minimum recommended wire size for different current levels and
operating temperatures. This table is derived from the National Electrical Code and is for
reference only. Local laws and conditions may have different requirements. The table is for
copper wire only.

Table 2.4-1

Minimum Wire Size Table

COPPER WIRE CURRENT CAPACITY

Single wire in open air, ambient temperature 86

o

F

Ampacities of Wire Types (w/ Temp Rating) @ 0-2000 Volts

Wire

Size

AWG

TW

UF

(140

o

F)

FEPW, RH, RHW, THW,

THWN, ZW,

THHW, XHHW

(167

o

F)

USE-2, XHH, XHHW, -2, TA,

TBS, SA, SIS, FEP

MI, RHW-2, THHN, ZW-2,

THWN-2, FEPB, RHH,

THHW, THW-2

(194

o

F)

0000

000

00

0

1

2

3

4

300

260

225

195

165

140

120

105

360

310

265

230

195

170

145

125

405

350

300

260

220

190

165

140

Ambient Ampacity Correction for above Wire types

Temp

o

F 140

o

F 167

o

F 194

o

F

96-104

105-113

114-122

123-131

132-140

141-158

159-176

0.82

0.71

0.58

0.41

- - -

- - -

- - -

0.88

0.82

0.75

0.67

0.58

0.35

- - -

0.91

0.87

0.82

0.76

0.71

0.58

0.41