Bulk fill pressure – Kinze ISOBUS Electronics Package (4900) Rev. 4/14 User Manual

Page 54

Advertising
background image

M0250

ISOBUS

50

Rev. 4/14

TM

Settings

In the Bulk Fill Pressure settings screen, the Low Pressure Threshold and Alarm Response time can be adjusted. The
pressure sensor can also be zeroed. Tap on the TABLE box to view pressure settings for all crops.

Zero Pressure Sensor Command
If the bulk fill fan is off and the sensor is still reading the pressure, this button can be used to set the zero point of the
sensor.

Gain
This controls how fast the bulk fill fan adjusts. If it is taking too long for the fan to adjust to the correct pressure, slowly
increase this number until the desired results are reached.

Zero Flow Offset
This sets how far the hydraulic valve will open when the fan is first turned on. If the fan is taking too long to come up to
the correct pressure, gradually increase this number until the desired result is reached. If the fan is overshooting the
pressure level when first turned on, decrease this value until the desired result is reached.

high/Low vacuum Threshold
This sets the threshold for where a visual and audible alarm for high or low pressure will appear while planting.

Alarm Response Time
This sets the amount of time the alarm condition must exist before the visual and audible alarm comes up. If the
response time is set to 10 seconds, the pressure has to be above the threshold for 10 seconds before a high bulk fill
pressure alarm is displayed.

Crop Settings
In this screen, pressure levels for all crops can be set. These will be the values used when a crop is selected from the
Crop Type screen.

The diagnostics section will display the sensor voltage, actual pressure, target pressure, and PWM duty cycle.

BULK FILL PRESSURE