Technical data, Terminal description axis modules, Digital inputs – Lenze i700 Manual User Manual
Page 51

Technical data
Terminal description
Axis modules
l
51
EDS700ACBA EN 4.0
Digital inputs
X2
Labelling
Description
DI1
Touch probe inputs
On double axis devices, there are
two of these connections. For the
assignment to the axes, the
designations "A" / "B" are used.
DI2
GD
Reference potential GND
i700P00x
Terminal data
Conductor cross−section
Tightening torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
flexible
0.2 ... 2.5
24 ... 12
−
−
3.5 x 0.6
X2
Electrical data
DI1
DI2
Rated voltage
24 V
in accordance with
IEC 61131−2
Voltage range
19.2 ... 28.8 V
Residual ripple
Max.
± 5 %
Current consumption
Max. 8 mA
Polarity reversal
protection
When polarity is reversed: no function and no
destruction.
GD
Reference potential
0 V
DI1
DI2
GD
B
DC 24 V
(+19.2...
+28.8 V)
DI1
DI2
GD
A
X2
i700M00x
Fig. 5
Wiring of X2
X2
Connection of digital inputs of axis module
A
1−axis module
B
Additionally for 2−axis module
DIx
Digital input
GD
Reference potential GND