Technical data, Ab c d e – Lenze i700 Manual User Manual
Page 63

Technical data
Terminal description
Axis modules
l
63
EDS700ACBA EN 4.0
1
0
2
3
a
b
c
d
e
U
V
W
BD1
(T1)
BD2
(T2)
PE
i700MOTL1
Fig. 4−4
Stripping lengths of the motor cable
[mm]
a
b
c
d
e
E70ACMSxxxx4xx1xxx
180
8
40
210
8
E70ACMSxxxx4xx2xxx
180
8
40
210
8
E70ACMSx0324xx1xxx
E70ACMSx0484xx1xxx
E70ACMSx0644xx1xxx
180
8
40
210
8
How to proceed:
1. Strip motor cable
0 as specified.
2. Fold back the shield of the motor cable
1 over the cable sheath.
3. Stabilise the shield with self−adhesive conductive foil
2 (recommendation).
4. Fix the shield and conductive foil with heat−shrinkable tube
3 on the cable sheath.
5. The terminals are directly suitable for the utilisation of flexible conductors. Short
circuits between the terminal connections are ruled out by the design if the
specified stripping length is met.
– Wire end ferrules can be used.
– If insulated wire end ferrules are used, it must be ensured that the effective
clamping length is not reduced by the plastic collar.
6. Apply the shields separately on the shield sheet using shield clamps (no strain relief).