Electrical installation

Important notes
Motor protection

6

l

86

EDS700ACBA EN 4.0

ƒ

In case of condensation, do not connect the controller to the mains voltage before
the moisture has evaporated completely.

ƒ

Provide unused control inputs and outputs with terminal strips.

6.1.3

Motor protection

ƒ

Extensive protection against overload by means of temperature monitoring:
– with KTY or PTC sensors of the resolvers or encoders
– with activated I

2

t monitoring

– Combination of the possible monitoring modes

ƒ

Only use motors which have a suitable insulation for the inverter operation:
– Insulation resistance: min. û = 1.5 kV, min. du/dt = 5 kV/

ms

– When using motors with an unknown insulation resistance, please contact your

motor supplier.

6.1.4

Interaction with compensation equipment

ƒ

Drive control systems only consume very little fundamental reactive power from the
supplying AC system. Therefore, compensation is not required.

ƒ

If the drive control systems are operated on supply systems by means of
compensation equipment, the compensation equipment must include chokes.
– For this purpose, please contact the supplier of the compensation equipment.