Technical data, Terminal description axis modules, External voltage supply – Lenze i700 Manual User Manual
Page 52

Technical data
Terminal description
Axis modules
l
52
EDS700ACBA EN 4.0
External voltage supply
X3
Labelling
Description
24E
24−V supply voltage of control electronics from a safely separated
power supply unit (SELV/PELV)
GE
Reference potential (GND)
i700P00x
Terminal data
Conductor cross−section
Tightening torque
!
[mm
2
]
[AWG]
[Nm]
[lb−in]
flexible
0.2 ... 2.5
24 ... 12
−
−
3.5 x 0.6
X3
Electrical data
24E
GE
Rated voltage
24 V
in accordance with
IEC 61131−2
Voltage range
19.2 ... 28.8 V
Residual ripple
Max.
± 5 %
Current consumption
See technical data,
^ 4.2.1
Polarity reversal
protection
When polarity is reversed: no function and no
destruction.
Cable protection
Circuit breaker with tripping characteristic B or C
Standard blade−type fuses
X21, X3
X3
DC 24 V
(+19.2...+28.8 V)
GND-I
GE 24E
i700M00x
Fig. 6
Wiring of X3
X3
Supply voltage connection of axis module control electronics, can be looped
through
24E
DC 24 V, acc. to IEC 61131−2, SELV/PELV
GE
Reference potential GND