Installation – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual

Page 13

Advertising
background image

Lenze 13466185 EDBSW03 v5

11

Installation

3.2.4

Control terminals

Terminal

Data for control connections

(printed in bold = Lenze setting)

CAN_GND

CAN earth ground

For reliable communication make sure terminal

CAN_GND is connected to CAN network

GND/common. If only two wires are used

(CAN_H and CAN_L) in the network, connect

CAN_GND to chassis/earth ground.

CAN_L

CAN low

If controller is located at either end of the

network, a terminating resistor (120Ω typical)

should be connected across CAN_L and CAN_H

CAN_H

CAN high

28

Digital input Start/Stop

LOW = Stop (

OFF

)

HIGH = Run Enable

R

i

= 3.3 kΩ

20

Internal DC supply for digital inputs

+12 V, max. 20 mA

E1

Digital input configurable with CE1

Activate fixed setpoint 1 (JOG1)

HIGH = JOG1 active

R

i

= 3.3 kΩ

E2

Digital input configurable with CE2

Direction of rotation

LOW = CW rotation

HIGH = CCW rotation

E3

Digital input/output configurable with CE3

Activate DC injection brake (DCB)

HIGH = DCB active

7

Reference potential

K12

Relay output (normally-open contact)

configurable with C08

Fault (TRIP)

AC 250 V / 3 A

DC 24 V / 2 A … 240 V / 0.22 A

K14

LOW = 0 … +3 V, HIGH = +12 … +30 V

Protection against contact

• All terminals have a basic isolation (single insulating distance)

• Protection against contact can only be ensured by additional measures i.e. double insulation