Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C37

Fixed setpoint 1

(JOG 1)

20.0 0.0 {Hz} 240

C38

Fixed setpoint 2

(JOG 2)

30.0 0.0 {Hz} 240

C39

Fixed setpoint 3

(JOG 3)

40.0 0.0 {Hz} 240

C46

Frequency setpoint

0.0 {Hz} 240 Display: Setpoint via CANopen or

function UP/DOWN

C50

Output frequency

0.0 {Hz} 240 Display

C53

DC bus voltage

0.0 {%} 255 Display

C54

Motor current

0.0 {%} 255 Display

C87

Motor rated speed

1390 300 {RPM} 32000 Set to motor nameplate speed

C89

Motor rated

frequency

50

10 {Hz} 1000 Set to motor nameplate frequency

C94

User password

0

0 999

Changing from “0” (no password), value

will start at 763

When set to a value other than 0,

must enter password at C00 to access

parameters

C99

Software version

Display, format: x.yz

c06

Holding time -

automatic DC

injection brake

(Auto-DCB)

0.0 0.0

{s}

999

0.0 = not active

999 = continuous brake

Automatic motor braking below 0.1 Hz

by means of motor DC current for the

entire holding time (afterwards: U, V,

W inhibited)

Confirm motor suitability for use with

DC braking

c20

I

2

t switch-off

(thermal motor

monitoring)

100 30 {%} 100

100% = smd rated output current

• Triggers

0C6

fault when motor current

exceeds c20 for too long

• Correct setting = (motor nameplate

current) / (smd output current rating) X

100%

Example: motor = 6.4 amps and smd

= 7.0 amps; correct setting = 91%

(6.4 / 7.0 = 0.91 x 100% = 91%)

NOTE

Do not set above the rated motor current as listed on the motor dataplate. The

motor thermal overload function is UL approved as a motor protection device. If

line power is cycled, the motor thermal state is reset to cold state. Cycling power

after an overload fault may result in reducing the motor life.

c21

Motor Overload

Type

00

00 Speed Compensation

Reduces the allowable continuous

current when operating below

30Hz.

Ir

100%

60%

30 f

1

0

Ir: rated current (%), f: motor frequency (Hz)

01 No Speed Compensation

Example: Motor is cooled by forced

ventilation as apposed to shaft

mounted, self cooling fans.

c40

Frequency setpoint

via keys

0.0 0.0

{Hz}

240 Only active if C01 = 0, 1