Lenze 13466185 EDBSW03 v5

17

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

c42

Start condition

(with mains on)

1

0 Start after LOW-HIGH change at

terminal 28

See also c70

1 Auto start if terminal 28 = HIGH

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to

personnel! Automatic starting/restarting should only be used on equipment that is

inaccessible to personnel.

c60

Mode selection

for c61

0

0 Monitoring only

c60 = 1 allows the keys

to adjust

speed setpoint (c40) while monitoring

c61

1 Monitoring and editing

c61

Present status/error

status/error message

Display

• Refer to Section 5 for explanation of

status and error messages

c62

Last error

error message

c63

Last error but one

c70

Configuration TRIP

reset (error reset)

0

0 TRIP reset after LOW-HIGH

change at terminal 28, mains

switching, or after LOW-HIGH

change at digital input “TRIP reset”

1 Auto-TRIP reset

Auto-TRIP reset after the time set in

c71

More than 8 errors in 10 minutes will

trigger

rSt

fault

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to

personnel! Automatic starting/restarting should only be used on equipment that is

inaccessible to personnel.

c71

Auto-TRIP reset

delay

0.0 0.0

{s}

60.0 See c70

c78

Operating time

counter

Display

Total time in status “Start”

0...999 h: format xxx

1000...9999 h: format x.xx (x1000)

10000...99999 h: format xx.x (x1000)

c79

Mains connection

time counter

Display

Total time of mains = on

CANopen / System bus parameters

h42

Guard time

0

0

{ms}

65535

h42 x h43 = node life time

If RTR frame with ID = 0x700 + Node

ID (h50) is not received during the

node life time, the controller will react

according to h44

If heart beat message is enabled, the

guard function is disabled

h44 is only active when C01 = 3 and

h42 x h43 > 0

h43

Life time factor

0

0 255

h44

Guard time event

reaction

0

0 Not active
1 Inhibit
2 Quick stop

3 Trip fault

FC3

h45

Error behavior

1

0 transition to pre-operational

(only if current state is operational)

Specifies action taken by the drive when

it encounters a communication error

(ex. Node guarding event or Bus Off)

1 No state change
2 transition to stopped

h46

Message monitoring

time

0

0

{ms}

65535

h46 and h47 can be used to monitor

all valid messages (e.g. SDO, SYNC,

PDO...).

h46 = 0 or h47 = 0 disables message

monitoring function

h47 is only active when C01 = 3

h47

Message monitoring

time out reaction

0

0 Not active
1 Inhibit
2 Quick stop
3 Trip fault

FC3