Commissioning – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual

Page 16

Advertising
background image

14

Lenze 13466185 EDBSW03 v5

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

CE1

Configuration -

Digital input E1

1

1 Activate fixed setpoint 1 (JOG1)

• Use C37...C39 to adjust fixed

setpoints

• Activate JOG3: Both terminals =

HIGH

2 Activate fixed setpoint 2 (JOG2)

3 DC braking (DCB)

See also C36

4 Direction of rotation

LOW = CW rotation

HIGH = CCW rotation

5 Quick stop

Controlled deceleration to standstill,

active LOW; Set decel rate in C13

6 CW rotation
7 CCW rotation

CW rotation = LOW and CCW rotation =

LOW: Quick stop; Open-circuit protected

CE2

Configuration -

Digital input E2

4

8 UP (setpoint ramp-up)

UP = LOW and DOWN = LOW: Quick

stop; Use momentary NC contacts

9 DOWN (setpoint ramp-down)
10 TRIP set

Active LOW, triggers

EEr

(motor coasts

to standstill)

NOTE:

NC thermal contact from the

motor can be used to trigger this input

11 TRIP reset

See also c70

12 No action

can be used if Ex inputs are used only

as CANopen digital inputs

CE3

Configuration -

Digital input/output

E3

3

1...12 (same as above)

13...19 (reserved)

20 Ready

21 Fault

22 Motor is running

23 Motor is running - CW rotation

24 Motor is running - CCW rotation

25 Output frequency = 0 Hz

26 Frequency setpoint reached

27 Threshold (C17) exceeded

• 1...11 configures term. E3 as an input

• 20...30 configures term. E3 as a

current-sourcing (PNP) output rated

12 VDC / 50 mA

28 Current limit reached

• in either motor or generator mode

29 No action

• Output disabled

30 CANopen Control

• output controlled by RPDO (h66,h76 = 4)

Note
A

CFG

fault will occur under the following conditions:

• E1...E3 settings are duplicated (each setting can only be used once)

• One input is set to UP and another is not set to DOWN, or vice-versa

C08

Configuration

- Relay output

(terminals K14 and

K12)

1

Relay is energized if
0 Ready

1 Fault

2 Motor is running

3 Motor is running - CW rotation

4 Motor is running - CCW rotation

5 Output frequency = 0 Hz

6 Frequency setpoint reached

7 Threshold (C17) exceeded
8 Current limit reached

in either motor or generator mode

9 CANopen Control

Output controlled by RPDO (h66,h76 = 4)