Technical data, 2 ratings – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual

Page 9

Advertising
background image

Lenze 13466185 EDBSW03 v5

7

Technical data

2.2

Ratings

Type

Power

[kW]

Mains

Output Current

Voltage, frequency

Current

[A]

I

r

I

max

for 60 s

[A]

(1)

[A]

(2)

[A]

(1)

[A]

(2)

ESMD251W2SFA

0.25

1/N/PE 230/240 V

2/PE 230/240 V

(180 V - 0% … 264 V + 0 %)

50/60 Hz

(48 Hz - 0 % … 62 Hz + 0 %)

3.4

1.7

1.6

2.6

2.4

ESMD371W2SFA

0.37

5.0

2.4

2.2

3.6

3.3

ESMD551W2SFA

0.55

6.0

3.0

2.8

4.5

4.2

ESMD751W2SFA

0.75

9.0

4.0

3.7

6.0

5.5

ESMD152W2SFA

1.5

14.0

7.0

6.4

10.5

9.6

ESMD222W2SFA

2.2

21.0

9.5

8.7

14.3

13.1

ESMD371W2TXA

0.37

3/PE 230/240 V

(180 V - 0% … 264 V + 0 %)

50/60 Hz

(48 Hz - 0 % … 62 Hz + 0 %)

2.7

2.4

2.2

3.6

3.3

ESMD751W2TXA

0.75

5.1

4.2

3.9

6.3

5.9

ESMD112W2TXA

1.1

6.9

6.0

5.5

9.0

8.3

ESMD152W2TXA

1.5

7.9

7.0

6.4

10.5

9.6

ESMD222W2TXA

2.2

11.0

9.6

8.8

14.4

13.2

ESMD302W2TXA

3.0

13.5

12.0

11.0

18.0

16.5

ESMD402W2TXA

4.0

17.1

15.2

14.0

22.8

21.0

(1)

For rated mains voltage and carrier frequencies 4, 6, 8 kHz

(2)

For rated mains voltage and carrier frequency 10 kHz

Advertising
This manual is related to the following products: