Commissioning – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual

Page 20

Advertising
background image

18

Lenze 13466185 EDBSW03 v5

Commissioning

(1)

These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

h48

Monitoring timeout

status

Bits:

• Read-only

• Indicates cause of FC3 fault, inhibit, or

quick stop (depending on the settings

of h44, h47, h65, h75)

0 Guard time timeout
1 No valid message received
2 RPD01 timeout
3 RPD02 timeout
4 CAN initialization fault
5

Bits 5…7 create a binary number from 0

to 7 indicating the number of overflows

in the receive buffers (h49 bits 6 and 7)

6 Recieve buffers overflow
7

h49

CAN controller

status value (8-bit

value)

Bits:

• Read-only

• CAN warnings and errors

0 Receive/transmit error warning flag

(96 or more errors)

1 Receive error warning flag (96 or

more receive errors)

2 Transmit error warning flag (96 or

more transmit errors)

3 Receive error passive flag (128 or

more receive errors)

4 Transmit error passive flag (128 or

more transmit errors)

5 Bus-off error flag
6 Receive buffer 0 overflow flag
7 Receive buffer 1 overflow flag

h50

(1)

CAN address (Node

ID)

1

1 127 If h53 = 0, 1: maximum setting = 63

h51

(1)

CAN baud rate

5

0 10 kbps (max distance = 5000m)
1 20 kbps (max distance = 2500m)
2 50 kbps (max distance = 1000m)
3 125 kbps (max distance = 500m)
4 250 kbps (max distance = 250m)
5 500 kbps (max distance = 100m)

h52

(1)

CAN bootup mode

0

0 Pre-operational

• h52 = 0: Controller enters pre-

operational state

• h52 = 1: Controller enters operational

state automatically (Slave with

autostart enabled 0x1F80 NMT

bootup - bit 2)

• h52 = 2: Controller sends “NMT start

all nodes” after boot-up time (h55)

and enters operational state (not

NMT master)

1 Operational

2 Pseudo-master mode