Commissioning – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual

Page 27

Advertising
background image

Lenze 13466185 EDBSW03 v5

25

Commissioning

WORD0 - C0135 control word

Bit

h66 / h76 setting = 4

0

JOG1, JOG2, JOG3

0 = C46 active

1 = JOG1 (C37) active

2 = JOG2 (C38) active

3 = JOG3 (C39) active

1

2

Direction of rotation

0 = CW (forward)

1 = CCW (reverse)

3

Quick stop

0 = Quick stop not active

1 = Quick stop active

4

reserved

5

reserved

6

reserved

7

reserved

8

reserved

9

Controller inhibit

0 = No controller inhibit

1 = Controller inhibit

10

reserved

11

TRIP reset

TRIP reset on transition from 0 to 1

12

reserved

13

reserved

14

DC brake

0 = DC brake not active

1 = DC brake active

15

reserved

WORD1

Speed signed scaled +/- 16384 == C11

(max frequency)

Example 1: Requested setpoint = CW at

34.5 Hz and C11 = 50.0Hz:

Setpoint = roundup(34.5 * 16384/50) = 11305

= 0x2C29

Example 2: Requested setpoint = CCW at

44.5 Hz and C11 = 50.0Hz:

= - roundup(44.5 * 16384/50) = -14582 = 0xC70A

Note:

Setpoint sign overrides Bit 2 in WORD0

WORD2

Digital outputs (RELAY + E3)

Bit 0 - RELAY - (if C08 set to selection 9)

Bit 1 - E3 (if CE3 set to selection 30)

WORD3

reserved (not evaluated)

Advertising
This manual is related to the following products: