Commissioning – Lenze SMD 0-25kW-4-0kW Basic I/O User Manual

Page 30

Advertising
background image

28

Lenze 13466185 EDBSW03 v5

Commissioning

WORD0 - Statusword 0x6041

Bit

h86 / h96 setting = 4

WORD0- Statusword 0x6041

Bit

h86 / h96 setting = 5

0

0 = Not ready to switch on

1 = Ready to switch on

0

0 = Not ready to switch on

1 = Ready to switch on

1

0 = Not switched on

1 = Switched on

1

0 = Not switched on

1 = Switched on

2

0 = operation disabled

1 = operation enabled

2

0 = operation disabled

1 = operation enabled

3

0 = No fault

1 = Fault

3

0 = No fault

1 = Fault

4

0 = Voltage disabled

1 = Voltage enabled

Note:

On smd controller, this is

always enabled

4

0 = Voltage disabled

1 = Voltage enabled

Note:

On smd controller, this is

always enabled

5

0 = Quick stop active

1 = Quick stop not active

5

0 = Quick stop active

1 = Quick stop not active

6

Switch on disabled

On smd controller this is always 0

(switch on enabled)

6

Switch on disabled

On smd controller this is always 0

(switch on enabled)

7

0 = No warning

1= Warning

7

0 = No warning

1= Warning

8

Manufacturer specific

8

Manufacturer specific

9

Remote

0 = C01 < > 2 and 3

1 = C01 = 2 or 3

9

Remote

0 = C01 < > 2 and 3

1 = C01 = 2 or 3

10

Target reached

0 = Setpoint not reached

1 = Setpoint reached

10

Target reached

0 = Setpoint not reached

1 = Setpoint reached

11

Internal limit

0 = Internal limit not active

1 = Internal limit active

11

Internal limit

0 = Internal limit not active

1 = Internal limit active

12

reserved

12

reserved

13

reserved

13

reserved

14

reserved

14

reserved

15

reserved

15

reserved

WORD1

Signed output frequency read from C50

RPM is calculated based on C50, C87, and C89

Example 1 (C87 = 1390 RPM, C89 = 50 Hz):

CW at 25.0 Hz = 25.0 x 1390/50 = 695 = 0x02B7

Example 2 (C87 = 1390 RPM, C89 = 50 Hz):

CCW at 44.5 Hz = - (44.5 x 1390/50) = - 1237 =

0xFB2B