Installation 3 installation, Warning – Lenze SMD 0-25kW-4-0kW User Manual
Page 10
![background image](/manuals/565708/10/background.png)
a
4 x M4
2,4 Nm
21 lb-in
c
a1
b1
b2
>50
>50
>15
>15
b
smd002
8
Lenze 13435747 EDBSX03 v17
EN, DE, FR, IT, ES
Installation
3
Installation
3.1
Mechanical installation
3.1.1 Dimensions and mounting
Type
a [mm]
a1 [mm]
b [mm]
b1 [mm]
b2 [mm]
c [mm]
m [kg]
ESMD251X2SFA
93
84
146
128
17
83
0.5
ESMD371X2SFA
ESMD551X2SFA
93
84
146
128
17
92
0.6
ESMD751X2SFA
ESMD152X2SFA
114
105
146
128
17
124
1.2
ESMD222X2SFA
114
105
146
128
17
140
1.4
ESMD371X2TXA
93
84
146
128
17
83
0.5
ESMD751X2TXA
93
84
146
128
17
92
0.6
ESMD112X2TXA
93
84
146
128
17
141
1.2
ESMD152X2TXA
ESMD222X2TXA
114
105
146
128
17
140
1.4
ESMD302X2TXA
114
105
146
128
17
171
1.9
ESMD402X2TXA
114
105
146
100
17
171
1.7
WARNING!
Drives must not be installed where subjected to adverse environmental conditions
such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive
vibration or excessive temperatures. Contact Lenze for more information.