Commissioning – Lenze SMD 0-25kW-4-0kW User Manual

Page 19

Advertising
background image

Lenze 13435747 EDBSX03 v17

EN, DE, FR, IT, ES

17

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

c70

Configuration TRIP

reset (error reset)

0

0 TRIP reset after LOW-HIGH

change at terminal 28, mains

switching, or after LOW-HIGH

change at digital input “TRIP reset”

1 Auto-TRIP reset

• Auto-TRIP reset after the time set in

c71

• More than 8 errors in 10 minutes will

trigger

rSt

fault

WARNING!

Automatic starting/restarting may cause damage to equipment and/or injury to

personnel! Automatic starting/restarting should only be used on equipment that is

inaccessible to personnel.

c71

Auto-TRIP reset delay 0.0 0.0 {s} 60.0 See c70

c78

Operating time

counter

Display

Total time in status “Start”

0...999 h: format xxx

1000...9999 h: format x.xx (x1000)

10000...99999 h: format xx.x (x1000)

c79

Mains connection

time counter

Display

Total time of mains = on

c81

PI setpoint

0.0 c86 c87

c82

S-ramp integration

time

0.0 0.0 {s} 50.0 • c82 = 0.0: Linear accel/decel ramp

• c82 > 0.0: Adjusts S-ramp curve for

smoother ramp

c86

Minimum feedback

0.0 0.0 999 • Select feedback signal at C34

• If feedback is reverse-acting, set

c86>c87

c87

Maximum feedback

100 0.0 999

d25

PI setpoint accel/

decel

5.0 0.0 {s} 999 Sets rate of change for PI setpoint

d38

PI mode

0

0 PI disabled
1 PI enabled: normal-acting

When feedback (terminal 8) exceeds

setpoint, speed decreases

2 PI enabled: reverse-acting

When feedback (terminal 8) exceeds

setpoint, speed increases

d46

Feedback minimum

alarm

0.0 0.0 999

See C08, selections 9 and 10

d47

Feedback maximum

alarm

0.0 0.0 999