Troubleshooting and fault elimination

Status

Cause

Remedy

e.g.

50.0

Present output frequency

Trouble free operation

OFF

Stop

(outputs U, V, W inhibited)

LOW signal at terminal 28

Set terminal 28 to HIGH

stP

Output frequency = 0 Hz

(outputs U, V, W inhibited)

Setpoint = 0 Hz (C31 = 0)

Setpoint selection

Quick stop activated through digital

input

Deactivate Quick stop

br

DC-injection brake active

DC-injection brake activated

• via digital input

• automatically

Deactivate DC-injection brake

• digital input = LOW

• automatically after holding time

c06 has expired

CL

Current limit reached

Controllable overload

Automatically (see C22)

LU

Undervoltage on DC bus

Mains voltage too low

Check mains voltage

dEC

Overvoltage on DC bus during

deceleration (warning)

Excessively short deceleration time

(C13, c03)

Automatically if overvoltage
< 1 s,

OU

, if overvoltage > 1 s

nEd

No access to code

Can only be changed when the
controller is in

OFF

Set terminal 28 to LOW

Error

Cause

Remedy

(1)

cF

Data on EPM not valid

Data not valid for controller

• Use EPM providing valid data

• Load Lenze setting

CF

Data error

GF

OEM data not valid

F1

EPM error

EPM missing or defective

Power down and replace EPM

CFG

Digital inputs not

uniquely assigned

E1...E3 assigned with the same

digital signals

Each digital signal can only be

used once

Either just “UP” or “DOWN” used

Assign the missing digital signal to

a second terminal

EEr

External error

Digital input “TRIP set” is active

Remove external error

F2...F0,

JF

Internal fault

Please contact Lenze

LC

Automatic start inhibited

c42 = 0

LOW-HIGH signal change at

terminal 28

0C1

Short-circuit or overload

Short-circuit

Find reason for short-circuit; check

motor cable

Excessive capacitive charging

current of the motor cable

Use shorter motor cables with lower

charging current

Acceleration time (C12, c01) too

short

• Increase acceleration time

• Check controller selection

Defective motor cable

Check wiring

Internal fault in motor

Check motor

Frequent and long overload

Check controller selection

5

Troubleshooting and fault elimination