Troubleshooting and fault elimination

Error

Cause

Remedy

(1)

0C2

Earth fault

Grounded motor phase

Check motor/motor cable

Excessive capacitive charging

current of the motor cable

Use shorter motor cables with lower

charging current

0C6

Motor overload (I

2

t overload)

Motor is thermally overloaded,

due to:

• impermissable continuous current

• frequent or too long acceleration

processes

• Check controller selection

• Check setting of c20

0H

Controller overtemperature

Controller too hot inside

• Reduce controller load

• Improve cooling

OU

Overvoltage on DC bus

Mains voltage too high

Check mains voltage

Excessively short deceleration time

or motor in generator mode

Increase deceleration time or use

dynamic braking option

Earth leakage on the motor side

Check motor/motor cable

(separate motor from controller)

rSt

Faulty auto-TRIP reset

More than 8 errors in 10 minutes

Depends on the error

Sd5

Loss of 4-20 mA reference

4-20 mA signal is below 2 mA

(C34 = 4)

Check signal/signal wire

SF

Single phase fault

A mains phase has been lost

Check mains voltage

(1) The drive can only be restarted if the error message has been reset; see c70

NOTE

In the event of an “OC6” (Motor Overload) failure there is a 3-minute delay before resetting

is possible. This is a requirement of UL508C. This delay is intended to allow time for the

motor to cool.
If power is removed when the drive is in an “OC6” fault state, when the power is restored

the “OC6” fault will still be present and the delay will still be active even if power was

removed for longer than 3 minutes.