Commissioning, 3 parameter menu – Lenze SMD 0-25kW-4-0kW User Manual

Page 15

Advertising
background image

Lenze 13435747 EDBSX03 v17

EN, DE, FR, IT, ES

13

Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Lenze

Selection

C00

Password entry

0

0 999 Visible only when password is active

(see C94)

C01

Setpoint source

0 Analog input (terminal 8; see C34)

1 Code c40

Observe notes about c40

C02

Load Lenze setting

0 No action/loading complete

• C02 = 1... 4 only possible with

OFF

• C02 = 2 : C11, C15 = 60 Hz

1 Load 50 Hz Lenze settings

2 Load 60 Hz Lenze settings

3 Load OEM settings

4 Translate

WARNING!

C02 = 1... 3 overwrites all settings! TRIP circuitry may be disabled!

Check codes CE1...CE3.
NOTE

If an EPM that contains data from a previous software version is installed, C02 =

4 converts the data to the current version.

CE1

Configuration -

Digital Input E1

1

1 Activate fixed setpoint 1 (JOG1)

• Use C37...C39 to adjust fixed setpoints

• Activate JOG3: Both terminals = HIGH

2 Activate fixed setpoint 2 (JOG2)

3 DC braking (DCB)

See also C36

4 Direction of rotation

LOW = CW rotation

HIGH = CCW rotation

5 Quick stop

Controlled deceleration to standstill,

active LOW; Set decel rate in C13 or

c03

6 CW rotation
7 CCW rotation

CW rotation = LOW and CCW rotation =

LOW: Quick stop; Open-circuit protected

CE2

Configuration -

Digital Input E2

4

8 UP (setpoint ramp-up)

UP = LOW and DOWN = LOW: Quick

stop; Use momentary NC contacts

9 DOWN (setpoint ramp-down)
10 TRIP set

Active LOW, triggers

EEr

(motor coasts

to standstill)

NOTE:

NC thermal contact from the

motor can be used to trigger this input

CE3

Configuration -

Digital Input E3

3

11 TRIP reset

See also c70

12 Accel/decel 2

See c01 and c03

13 Deactivate PI

Disables PI function for manual control

14 Activate fixed PI setpoint 1

• Use C37...C39 to adjust fixed

setpoints

• Activate fixed PI setpoint 3: Both

terminals = HIGH

15 Activate fixed PI setpoint 2

NOTE
A

CFG

fault will occur under the following conditions:

• E1...E3 settings are duplicated (each setting can only be used once)

• One input is set to UP and another is not set to DOWN, or vice-versa

4.3

Parameter menu

Advertising