Installation, 3 connection diagram, Installation after a long period of storage stop – Lenze SMD 0-25kW-4-0kW User Manual

Page 12: Danger, Stop

Advertising
background image

10

Lenze 13435747 EDBSX03 v17

EN, DE, FR, IT, ES

Installation

Installation After a Long Period of Storage

STOP!

Severe damage to the drive can result if it is operated after a long period of storage or inactivity without

reforming the DC bus capacitors.
If input power has not been applied to the drive for a period of time exceeding three years (due to storage,

etc), the electrolytic DC bus capacitors within the drive can change internally, resulting in excessive

leakage current. This can result in premature failure of the capacitors if the drive is operated after such

a long period of inactivity or storage.
In order to reform the capacitors and prepare the drive for operation after a long period of inactivity, apply
input power to the drive for 8 hours prior to actually operating the motor

.

3.2.3 Connection diagram

PE PE

U V W

PE

L1 L2/N

PE

PE

PES

M

3~

smd

8 9 20

7

28

28

E1

E1

E2

E2

E3

E3

K14 K12

+10V

+12V

COM

AIN

1k … 10k

7

PE

N

L3

L2

L1

1/N/PE 180 V - 0 %

… 264 V + 0 %

48 Hz

… 62 Hz

8

7

250

0 ...20 mA

4 ...20 mA

+

_

PE

L1

L2/N

PE

N

L3

L2

L1

2/PE 180V - 0%

… 264V + 0

48 Hz … 62 Hz

0.5 Nm / 4.5 lb-in

6 mm / 0.24 in

PES

PES

PES

0.2 Nm / 2 lb-in

6 mm / 0.24 in

< 1 mm² / AWG 26… 16

_

+12 VDC - 0 %

+30 VDC + 0 %

L1

L2

PE

N

L3

L2

L1

3/PE 180V - 0%

… 264V + 0 %

48 Hz … 62 Hz

L3

PE

smd003

DANGER!

• Hazard of electrical shock! Circuit potentials are up to 240 VAC above earth ground. Capacitors retain

charge after power is removed. Disconnect power and wait until the voltage between B+ and B- is

0 VDC before servicing the drive.

• Do not connect mains power to the output terminals (U,V,W)! Severe damage to the drive will result.

• Do not cycle mains power more than once every three minutes. Damage to the drive will result.

STOP!

If the kVA rating of the AC supply transformer is greater than 10 times the input kVA rating of the drive(s),

an isolation transformer or 2-3% input line reactor must be added to the line side of the drive(s).