Safety information – Lenze SMD 0-25kW-4-0kW User Manual

Page 7

Advertising
background image

Lenze 13435747 EDBSX03 v17

EN, DE, FR, IT, ES

5

Safety information

Note for UL approved system with integrated controllers

UL warnings are notes which apply to UL systems. The documentation contains special information

about UL.

Warnings!

• Integral solid state protection does not provide branch circuit protection. Branch

circuit protection must be provided in accordance with the National Electrical

Code and any additional local codes. The use of fuses or circuit breakers is the

only approved means for branch circuit protection.

• When protected by CC and T Class Fuses, suitable for use on a circuit capable

of delivering not more than 200,000 rms symmetrical amperes, at the maximum

voltage rating marked on the drive.

• Additionally suitable when protected by a circuit breaker having an interrupting

rating not less than 200,000 rms symmetrical amperes, at the maximum

voltage rating marked on the drive. (Excludes ESMD113_4T_, ESMD112_2Y_,

ESMD113 _ 2T_, ESMD152_ 2Y_, ESMD153 _ 2T_, ESMD222_ 2Y_,

ESMD223_4T_, ESMD402_2T_, ESMD552_2T_, ESMD752_2T ESMD153_4T_,

and ESMD183_4T_).

• Use minimum 75°C copper wire only, except for control circuits.
• For control circuits, use wiring suitable for NEC Class 1 circuits only.
• Torque Requirements are listed in section 3.2.3, Connection diagram.
• Shall be installed in a pollution degree 2 macro-environment.

DANGER!

Risk of Electric Shock! Capacitors retain charge for approximately 180 seconds after power

is removed. Disconnect incoming power and wait at least 3 minutes before touching the

drive.

WARNING!

The opening of branch-circuit protective device may be an indication that a fault has been

interrupted. To reduce the risk of fire or electric shock, current carrying parts and other

components of the controller should be examined and replaced if damaged.

Advertising